Fire safety for data centres and offices
In a data centre water is not an option for suppression, and downtime is itself a loss. Protection starts with detecting fire before it develops.
Server and equipment rooms are usually protected with clean agent systems that leave no residue on equipment, early smoke detection, and room sealing that holds the agent concentration. Corporate offices need escape design for open-plan floors and alignment with the parent company's standards.
We have worked on stc data centres, more than 20 Mobily sites, the Schlumberger, Honeywell and Yokogawa headquarters in Dhahran Techno Valley, and Alinma Bank and NBK branches. For multi-site programmes we set one standard and apply it site by site.
What the design has to get right
- Clean agent suppression for equipment rooms
- Early smoke detection
- Room integrity to hold agent concentration
- Escape design for open-plan floors
- One standard across multi-site programmes
Why very early detection
The strong airflow in a server room dilutes smoke before it reaches a conventional ceiling detector. Aspirating detection is used instead: it samples the room air continuously and alerts at very low smoke concentrations.
The practical benefit is a staged response: a first alert lets the team inspect and isolate the equipment, then an alarm, then gas discharge as the last line. Many incidents end at the first stage with no loss of service.
What makes a clean agent system fail
A gas system extinguishes by reaching a set concentration in the room and holding it long enough. Anything that prevents that defeats the system, even with sound cylinders:
- Unsealed cable openings, or a room that does not hold the agent.
- Changing the room volume or adding a raised floor without recalculating the agent quantity.
- Air conditioning that keeps running and dampers that stay open on discharge.
- Doors left open during operation.
- Cylinders whose weight or pressure is not checked periodically.
Office headquarters: what changes with every re-partition
An office floor is re-partitioned several times over a building's life. Turning open plan into closed offices and meeting rooms changes sprinkler and detector coverage, changes the travel distance to exits, and can hide sounders and beacons.
We therefore check each new layout against the existing systems before work starts and record the change in the building file, so the approved drawing still matches reality at any inspection.
Our projects in this sector
Related services
Common questions
Usually a clean agent system with early detection; the agent and quantity are set after studying the room's volume, integrity and equipment.